Fire Safety Science Digital Archive

AOFST Symposiums

Comparison Of Rise Time Of Free Smoke Plume Front Predicted By A Field Model With Full-Scale Experiments

Hu, L.H., Chow, W.K., Huo, R., Li, Y.Z. and Wang, H.B., 2004. Comparison Of Rise Time Of Free Smoke Plume Front Predicted By A Field Model With Full-Scale Experiments. AOFST 6


ABSTRACT

A fire field model Fire Dynamics Simulator (FDS) version 3.10 will be used to predict the rise time of free buoyant plume front in this paper. Numerical simulations were on configurations same as a set of full-scale burning tests carried out recently in a big atrium. Track of the plume front was deduced from ‘sudden temperature rise’ on the numerical thermocouples. Results show that the rise time of these plume fronts predicted by FDS version 3.10 are slightly shorter than the experimental data.



View Article

Member's Page | Join IAFSS | Author's Site

Copyright © International Association for Fire Safety Science